DCM 200 Installation
Page 27
6.3. Contact Set, Flow Switch F
Switching from Water Meter to Contact Set clears log.
Contact Set
[typical Aquatic uses
are sensor flow
switch, main
recirculation flow
switch, auto fill
switch, or low
chemical level alarm]
User selects Contact Set
Contact sets are ON when closed and OFF when
open. ON time is logged.
Contact sets used for interlocking, prevent relays
from turning ON when contact set is OFF, or open.
Contact sets may be configured as ‘inverted’ to act
and display as ON when they are OFF.
6.4. Frequency Controlled Pumps
Feed Rate Setting
The controller knows the pump’s mL/stroke and maximum stroke rate (Maximum SPM), based on the
ProMinent pump model entered, or the values you entered for ‘Other’.
Once you select the pump feed method or control mode, the controller sets the optimum Pump Speed.
Sensor
Controlled
pH
ORP
TurnOFF :
pH or ORP setpoint
100%ON :
pH or ORP setpoint
Proportional control.
As the pool or spa chemistry changes from swimmers or
Chlorine feed, the pH rises.
The acid pump is OFF at pH < TurnOFF.
The pump speed increases linearly between TurnOFF
and 100% TurnON setpoints.
ORP: Oxidant
As the pool or spa operates, contaminants are
introduced, Chlorine is consumed and the ORP falls.
The hypochlorite pump is OFF at ORP > TurnOFF
The pump speed increases linearly between TurnOFF
and 100%ON setpoints.
Feed
mL/minute setpoint
Pump feeds at user set rate unless flow switch interlocks
(turns OFF) feed. [Not normally used in pool and spa
applications.]
Events
Start Day# & Time
Feed Volume
Pumps user set volume at maximum SPM. (Probe Wash)
Cycling
User sets cycle period in
minutes and ON volume in mL.
Pumps user set volume (1mL to 10L) at maximum SPM
at the start every user set period if above TurnON
setpoint. [Not typically used in Pool and Spas]